English
Furkan Engineering had been running for the world's security since 1992
 
About Us | Career | +90 212 483 17 83 | Contact  

 

Main Page > Disabled Refuge Systems > Vox-Ignis Lexicomm Master Stations > Vox-Ignis ViLX-228 0 Line Repeater Station

 

 

Vox-Ignis ViLX-228 0 Line Repeater Station

  Vox-Ignis ViLX-228 0 Line Repeater Station

All Lexicomm Emergency Voice Communications Systems (EVCS) are designed to comply fully with the requirements of BS5839-9:2011 for use as a fire telephone system (FT), disabled refuge system (DRS) or as a combined system when both fire telephones and disabled refuge call points are required.

General Features:
  • Compact Design
  • Fully Compliant to BS5839-9: 2011
  • Integrated Assist Call and acknowledge meeting BS8300
  • 1.5A EN54-4:A2 PSU
  • Full Duplex operation
  • Wall mount enclosure
  • Lockable handset cover
  • Expandable from 2 to 8 lines
  • Inbuilt networking

 


Price : On Request

The Lexicomm LX228 repeater station consists of a self-contained enclosure housing a master handset, an EN54-4:A2 2006 power supply & battery charger and can be surface or flush mounted.

The case is made from powder coated zintec, with a smoked perspex door covering the handset. 20mm cable knock-outs are provided for all necessary cables as well as space for the backup 12V 7AH VRSLA battery.

The repeater station is microprocessor controlled, it has an identical appearance to a LX228 master station and can control a maximum of 8 lines. Lines auto identify by flashing Red for EVCS calls, Blue for assist calls or flashing Green for Connected calls as detailed in BS5839pt9:2011.

Assist Calls can be acknowledged by pressing the zone key (as required by BS8300) and will return to alarm if not reset within two minutes.

A maximum of one repeater station can be connected to a ViLX-228 master station, no configuration is required.

 
.
Technical Specification

POWER SUPPLY & CHARGER  
Supply Voltage : 230VAC +/- 10% 50/60Hz
Internal Supply : 5V, 16V, 27V DC
Supplies : Monitored Open, Short, Fuses, High Impedance
Protection : Deep discharge, Short, Thermal
Battery Type : 1 x 12V 7AH VRSLA
Main Fuses : 240V 1A HRC
Battery Fuses : 750mA PTC
Charge Current : 400mA
INPUTS  
Line Inputs : 2-8 in 2 line blocks
Remote Enables : Short to use
End of Line Resistor : 10KΩ
OUTPUTS  
Number : 2, Fault & In use
Type : Volt free relay
Contact : 30V DC 1A
CONTROL FUNCTIONS  
Buttons : 8 Zone keys
Zone LEDs (x8) : RGB Status leds
Fault LEDs : 3, PSU, System, General
Supply LEDs : 2, AC ,DC present
NETWORK CABLES  
Type : Enhanced*
Core : 2x2 core 1mm or 1.5mm
Distance : 500m
STANDARDS & COMPLIANCE  
EMC EN55103-1,EN55103-2
LVD EN60065
Product Family : BS5839-pt9, BS9999, BS8300
 
 
Other Products We Recommend

MIE-RC -Remote Controller
Price:On-Request
MIE-WMC-Wireless Contact
Price:On-Request
MIE-IWS - Indoor Sounder
Price:On-Request
 
     

  • Design and specifications are subject to change without prior notice.
 